Home > Products > Dry type Power Transformers : Dry type Power Transformers
            Subgroups List      

Dry type Power Transformers

rated 10kVA ÷ 1600 kVA


Miscellaneous

The transformers belonging to this class comply to the requirements of the Romanian standards (STAS 1703) or to the internationally recognized standards required by the customers, mainly IEC 726.


Conditions of operation

The transformers are meant to supply the inner auxiliaries of the power stations within the underground train stations and residential districts. The transformers are rated to operate in suitably ventilated closed rooms and are supplied from electrical grids free from the atmospheric surge voltages.

The ambient temperatures are:

  • max. ambient temperature: +40° C

  • max. air daily average temperature +30° C

  • min. air temperature -15° C

  • max. altitude: 1000 m above the sea level

Protection degree: IP00 or IP20


Construction features

  • The magnetic circuit is made of carlyte insulated, grain oriented, cold rolled silicous steel sheet

  • The windings are manufactured of glass-fiber and enamel insulated cooper wire, impregnated in electro-insulating varnish.

  • The winding types used are: cylindrical or helical on the LV side and layered or continuous, in flat coils on the HV side.

  • The voltage control on the HV side is achieved at a terminal plate, by means of riglets (bars).

  • The HV and LV connections are manufactured of glass fiber strip insulated copper buses.

  • The outlets are taken out on the transformer small side or top, on the HV side through bushings and on the LV one through buses.
    Function of the customer's request and with the manufacturer's agreement, the outlets may be located otherwise too: by performing the required changes of the overall dimensions.

  • The protection housing is made of steel sheet placed on a metal frame. At the top it is provided with louvers enabling air free flow.
    The transformer may be lifted by means of lugs provided on its structure.


Main accessories

  • HV bushings

  • LV buses

  • grounding terminal

  • undercarriage

  • housing


Technical specific features

  • operating frequency: 50 Hz

  • operating voltage : HV: 6; 10 kV; LV: 0.4 kV LV copper buses

  • voltage control range on the HV side± 2 x 2.5%; ± 5%; ± 10%

  • cooling type: ANAN

  • insulation class: F

  • permissible temperature rises in windings: 100° C


The main equipment sorts of the group are presented in the following table:

Rating
(kVA)
Voltage
(kV)
Uk
(%)
Po
(kW)
Pk
(kW)
Connection group Overall Weight
(kg)
Overall Dimensions
(LxWxH)(mm)
10 0.38/0.048 3 0.11 0.25 Dy11 140 700x300x440
25 0.38/0.052 4 0.17 0.4 Yyn0 240 850x355x530
40 0.38/0.122 4 0.24 0.68 Yy0 300 805x350x570
60 0.5/0.23 4 0.4 1 Yy0 450 950x510x780
100 10/0.4 3.5 0.86 1.05 Yy0 1045 1925x840x1060
160 6/0.47 8 0.55 2.8 Yyn0 746 1240x440x960
200 6.3/0.4 4 0.95 2.5 Yyn0 1085 1280x620x1258
250 20/0.4 6 1.3 3.2 Dyn5 1670 1640x676x1500
315 6/0.47 4 1.4 2.4 Yyn0 2125 2340x780x1725
400 6.3/0.4 6 1.5 3.8 Dyn5 1885 2200x1000x1350
630 6.3/0.66 6 1.75 6 Dy05 2600 2155x1030x1670
630 20/0.4 6 2.3 7.2 Dyn5 2485 1840x800x1620
750 13.8/0.4 8 1.9 6.5 Dyn11 3120 1750x850x1880
800 6/0.427 6 2.1 7 Dd6 2846 1630x790x1643
900 6/0.66 6.5 2.2 6.8 Dy11 3300 2150x800x1355
1000 6/0.4 6 2.5 8.5 Dyn5 3370 2200x1050x1840
1000 10/0.4 6 2.7 8.5 Dyn5 3640 2300x1100x1950
1600 6.3/0.4 6 3 11 Dyn-5 5655 2660x1050x2360
   
1.LV buses
2.HV bushing
3.Lifting lug
4.Name plate
5.Warning name plate
6.Alarms name plate
7.Grounding terminal
8.Undercarriage
9.Temperature microrelay
10.Shutter
11.Lifting lugs for housing
12.Removable cover