ELECTROPUTERE

POWER TRANSFORMERS

Home

About us

Products

Contacts

 

Oil Immersed Power Transformers

Dry type Power Transformers

Special Power Transformers


Home > Products > Oil Immersed Power Transformers : Three Phase for the Internal Services of the Nuclear Power Plant
            Subgroups List      

Three Phase Power Transformers for the Internal Services of the Nuclear Power Plant


Miscellaneous

The transformers contained in this group comply to the conditions imposed by STAS 1703/80 and IEC 76 standards, being intended to supply the own services of the nuclear power plant.


Conditions of operation

The transformers are intended to function in the N climatic area in accordance with the environment conditions required in the customer's specification, whose features and ambient temperature are:

  • max. altitude: 1000 m above the sea level

  • ambient temperature:

    • min. -35° C

    • max. +40° C with peaks at 42.5° C


Construction features

The transformers are achieved in proper condition so as to assure the quality required by AQ-04 norms.

  • The magnetic core is made of cold rolled silicous steel sheet.

  • The HV windings are of continuous type, the tapped ones are of continuous type, and the LV ones of helical type.

The on load tap changers M III 500 /72.5 kV type and 3M I-1500/24 kV type and are provided with possibilities of connection to the automatic voltage control device.

  • The tank is bell type or with cover, welded construction made of steel plate, being vacuum tested and guaranteed.

The tank and the platform (or the cover) are provided with all the mechanic accessories to install, carry and check the transformer good operation.


Main accessories

  • magnetic oil level indicator

  • Buchholz relay

  • oil and winding temperature indicator

  • current transformers

  • motofans

  • pressure relief device

  • HV, LV, MV bushings

  • radiators

  • oil conservator

  • control cabinet

  • oil draining and filtering valves

  • undercarriage (wheels)

  • OLTC

  • motor drive unit for OLTC

  • de-hydrating breather with silicage


Technical specific features

  • operating frequency: 50 Hz

  • voltage control on the HV side: ± 8 x 1.25%

  • cooling type: ONAN/ONAF


The main equipment sorts of the group are presented in the following table:

Rating
(MVA)
Voltage
(kV)
Uk
(%)
Po
(kW)
Pk
(kW)
Connection group Overall Weight
(kg)
Overall Dimensions
(LxWxH)(mm)
60/30/30 24/10.5/6.3 18.546 236Dyn1yn1 1105007670x5440x5575
60/30/30110/10.5/6.3 20.246 236YNyn0d1 1170008425x5090x5755
   
1.HV bushings
2.HV neutral bushing
3.LV bushings
4.LV neutral bushing
5.MV bushings
6.Oil conservator
7.On load tap changer
8.Motor drive for OLTC
9.Pressure relief device
10.Oil filtering valve
11.Radiator
12.Fan
13.Jacking supports
14.Oil draining and filtering valve
15.Buchholz relay
16.Magnetic oil level indicator
17.Control cabinet
18.Winding temperature indicator
19.Oil temperature indicator
20.Dehydrating breather
21.Wheels
Română | Home | Products