Three Phase Power Transformers for Drilling Plants
Miscellaneous
The transformers belonging to this class comply to the requirements in IEC 146.
They are self cooled, oil immersed, three phase power transformers, having the HV and LV outlets through bushings protected in a housing, for outdoor installation on a moving drilling platform.
Conditions of operation
Construction features
The magnetic circuit is made of carlyte insulated, grain oriented, cold rolled silicous steel sheet.
The windings are made of paper insulated copper or aluminium wire and they withstand short-circuits.
The winding types are: cylindrical or helical on the LV side and continuous in flat coils on the HV one, voltage control on the HV side takes place by means of a tap changer, operated only with the de-energized transformer.
The tank is cover type, made of welded steel sheet, stiffened with ribs and is provided with coolers made of elliptical tubes.
Main accessories
magnetic oil level indicator
oil conservator
dial type thermometer
double float Buchholz relay
tap changer operating device
draining valve
filling plugs
air breather
oil sampling plug
lifting lugs
grounding terminals
name plates
Technical specific features
The main equipment sorts of the group are presented in the following table:
Rating (kVA) | Voltage (kV) |
Uk (%) | Po (kW) |
Pk (kW) | Connection group |
Overall Weight (kg) | Overall Dimensions (LxWxH)(mm) |
| 630 |
6/0.4 |
6 |
1.3 |
6.5 |
Dyn5 |
2750 |
1850x1290x1700 |
| 1000 |
20/0.525 |
6 |
1.85 |
11.9 |
Yyn0 |
3000 |
1900x1000x2150 |
| 1000 |
20/0.66 |
5.5 |
1.8 |
10 |
Yyn0 |
3980 |
1930x1460x2170 |
| 1600 |
6/0.66 |
6 |
2.5 |
15.5 |
Yy0 |
5450 |
2200x1760x2230 |
| 1600(2400) |
6/0.66 |
6.25 |
3.3 |
23 |
Yyn0 |
6800 |
2650x2150x2530 |
| 2000 |
10/0.66 |
6 |
2.4 |
18.2 |
Yyn0 |
5570 |
2070x1400x2485 |
| 2000 |
20/0.66 |
6 |
2.45 |
18.2 |
Yyn0 |
5640 |
2070x1400x2485 |
| 1. | Oil conservator |
| 2. | Oil filling plug |
| 3. | Oil level indicator |
| 4. | Buchholz relay |
| 5. | Connection valve |
| 6. | Silicagel breather |
| 7. | Untanking part lifting lug |
| 8. | Lifting lug |
| 9. | Name plate |
| 10. | Dial type thermometer |
|
| 11. | Oil draining valve |
| 12. | Skid |
| 13. | Earthing terminal |
| 14. | HV bushing |
| 15. | LV bushing |
| 16. | Tap changer |
| 17. | LV protection box |
| 18. | Thermometer pocket |
| 19. | Wiring box |
|